Backflow assembly test: Main Street Taqueria
ApprovedFiled May 28, 2025 by Drew Stroud, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 28, 2025
- Assembly type
- RP
- Serial number
- A998858
- Size
- 1
- Test gauge serial
- G-6925
- Gauge calibration date
- Mar 2, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Stroud, current on the service date
- All required fields present
- Address matches parcel 021-58-01147
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.