Backflow assembly test: Golden Brewing Co
ApprovedFiled Dec 18, 2024 by Alex Ashby, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 18, 2024
- Assembly type
- RP
- Serial number
- Z540084
- Size
- 1 1/2
- Test gauge serial
- G-1871
- Gauge calibration date
- Oct 24, 2024
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Ashby, current on the service date
- All required fields present
- Address matches parcel 021-50-01153
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
2402 Old Church Way
Owner: Pruitt Holdings LLC
Parcel 021-50-01153