Back to the backflow review queue

Backflow assembly test: Riverside Dental

Approved

Filed Dec 2, 2025 by Cameron Danner, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 2, 2025
Assembly type
DC
Serial number
W416445
Size
1
Test gauge serial
G-8874
Gauge calibration date
Aug 5, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 021-93-01222
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1658 Hickory Trl
Owner: Marsh Holdings LLC
Parcel 021-93-01222