Back to the backflow review queue

Backflow assembly test: Blue Heron Dental

Filed Nov 28, 2026 by Cameron Danner, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 28, 2026
Assembly type
RP
Serial number
A903538
Size
1
Test gauge serial
G-5530
Gauge calibration date
Mar 17, 2026
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 021-13-01226
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

7372 Hickory Ct
Owner: Kessler Holdings LLC
Parcel 021-13-01226