Back to the backflow review queue

Backflow assembly test: 5698 Fox Run Rd

Approved

Filed Oct 1, 2025 by Avery Ramirez, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Oct 1, 2025
Assembly type
PVB
Serial number
B854296
Size
3/4
Test gauge serial
G-5345
Gauge calibration date
Apr 21, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-44-01008
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5698 Fox Run Rd
Owner: Shawn Stroud
Parcel 021-44-01008