Backflow assembly test: Riverside Pizza
ApprovedFiled Aug 3, 2024 by Riley Pruitt, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 3, 2024
- Assembly type
- RP
- Serial number
- W903880
- Size
- 2
- Test gauge serial
- G-4412
- Gauge calibration date
- Apr 13, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Pruitt, current on the service date
- All required fields present
- Address matches parcel 021-74-01304
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3488 Ridgeview Rd
Owner: Calloway Holdings LLC
Parcel 021-74-01304