Back to the backflow review queue

Backflow assembly test: Riverside Pizza

Approved

Filed Aug 10, 2025 by Morgan Stroud, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 10, 2025
Assembly type
RP
Serial number
W903880
Size
2
Test gauge serial
G-5012
Gauge calibration date
Apr 24, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 021-74-01304
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3488 Ridgeview Rd
Owner: Calloway Holdings LLC
Parcel 021-74-01304