Back to the backflow review queue
Backflow assembly test: 7778 Fox Run Dr
ApprovedFiled May 14, 2026 by Sam Nguyen, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- May 14, 2026
- Assembly type
- DC
- Serial number
- K780241
- Size
- 3/4
- Test gauge serial
- G-6393
- Gauge calibration date
- Sep 27, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Nguyen, current on the service date
- All required fields present
- Address matches parcel 025-66-01043
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7778 Fox Run Dr
Owner: Avery Wexler
Parcel 025-66-01043