Backflow assembly test: Two Rivers Taqueria

Filed Nov 26, 2026 by Riley Nguyen, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Nov 26, 2026
Assembly type
RP
Serial number
W116203
Size
1 1/2
Test gauge serial
G-7288
Gauge calibration date
Nov 1, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.7 psid
Relief valve opened at
2.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 025-93-01247
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Property

5182 Ridgeview Trl
Owner: Benton Holdings LLC
Parcel 025-93-01247