Backflow assembly test: 1646 Spring Branch Ln
ApprovedFiled Nov 8, 2026 by Reese Calloway, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 8, 2026
- Assembly type
- PVB
- Serial number
- A854890
- Size
- 1
- Test gauge serial
- G-1810
- Gauge calibration date
- May 13, 2026
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Calloway, current on the service date
- All required fields present
- Address matches parcel 025-81-01138
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.