Back to the backflow review queue

Backflow assembly test: Golden Market

Approved

Filed Nov 15, 2024 by Cameron Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 15, 2024
Assembly type
RP
Serial number
K523199
Size
4
Test gauge serial
G-3141
Gauge calibration date
May 17, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 025-64-01083
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5625 Hickory Dr
Owner: Benton Holdings LLC
Parcel 025-64-01083