Back to the backflow review queue

Backflow assembly test: 1163 Cedar Hollow Ct

Approved

Filed Dec 17, 2024 by Sam Nguyen, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Dec 17, 2024
Assembly type
PVB
Serial number
A136562
Size
1
Test gauge serial
G-3264
Gauge calibration date
Mar 22, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 025-88-01057
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1163 Cedar Hollow Ct
Owner: Morgan Lindqvist
Parcel 025-88-01057