Back to the backflow review queue

Backflow assembly test: Two Rivers Diner

Approved

Filed Aug 7, 2026 by Cameron Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 7, 2026
Assembly type
RP
Serial number
B728725
Size
1 1/2
Test gauge serial
G-9373
Gauge calibration date
Mar 7, 2026
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 025-93-01187
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

424 Fox Run Ct
Owner: Brandt Holdings LLC
Parcel 025-93-01187