Backflow assembly test: Corner Brewing Co
Needs reviewFiled Nov 22, 2026 by Jordan Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 22, 2026
- Assembly type
- RP
- Serial number
- Z311947
- Size
- 1
- Test gauge serial
- G-2127
- Gauge calibration date
- May 22, 2026
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 025-84-01171
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
4273 Turkey Hill Rd
Owner: Nguyen Holdings LLC
Parcel 025-84-01171