Backflow assembly test: Hilltop Animal Hospital
ApprovedFiled Aug 19, 2026 by Sam Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 19, 2026
- Assembly type
- RP
- Serial number
- K108487
- Size
- 4
- Test gauge serial
- G-8360
- Gauge calibration date
- Jan 31, 2026
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Nguyen, current on the service date
- All required fields present
- Address matches parcel 025-46-01305
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.