Back to the backflow review queue

Backflow assembly test: 4969 Old Church Dr

Approved

Filed Nov 3, 2025 by Avery Harlow, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 3, 2025
Assembly type
RP
Serial number
K787625
Size
3/4
Test gauge serial
G-7463
Gauge calibration date
Feb 5, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Harlow, current on the service date
  • All required fields present
  • Address matches parcel 025-70-01072
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4969 Old Church Dr
Owner: Riley Ramirez
Parcel 025-70-01072