Back to the backflow review queue

Backflow assembly test: 4969 Old Church Dr

Filed Nov 19, 2026 by Riley Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 19, 2026
Assembly type
RP
Serial number
K787625
Size
3/4
Test gauge serial
G-1765
Gauge calibration date
Jun 15, 2026
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 025-70-01072
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

4969 Old Church Dr
Owner: Riley Ramirez
Parcel 025-70-01072