Backflow assembly test: 8879 Cedar Hollow Rd

Approved

Filed Dec 5, 2023 by Jordan Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 5, 2023
Assembly type
DC
Serial number
B132851
Size
1
Test gauge serial
G-8808
Gauge calibration date
May 11, 2023
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 025-41-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8879 Cedar Hollow Rd
Owner: Emerson Stroud
Parcel 025-41-01340