Back to the backflow review queue

Backflow assembly test: Riverside Bakery

Approved

Filed May 14, 2023 by Quinn Wexler, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
May 14, 2023
Assembly type
RP
Serial number
W588044
Size
2
Test gauge serial
G-2784
Gauge calibration date
Jul 18, 2022
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 027-47-01334
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3125 Laurel Way
Owner: Lindqvist Holdings LLC
Parcel 027-47-01334