Backflow assembly test: Main Street Medical Offices
ApprovedFiled Nov 8, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 8, 2026
- Assembly type
- RP
- Serial number
- K769067
- Size
- 1
- Test gauge serial
- G-1030
- Gauge calibration date
- Jun 6, 2026
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Whitcomb, current on the service date
- All required fields present
- Address matches parcel 027-96-01073
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5807 Orchard Trl
Owner: Harlow Holdings LLC
Parcel 027-96-01073