Back to the backflow review queue

Backflow assembly test: 3892 Old Church Trl

Approved

Filed Jun 27, 2026 by Avery Lindqvist, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 27, 2026
Assembly type
RP
Serial number
B980660
Size
3/4
Test gauge serial
G-7087
Gauge calibration date
Apr 23, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 027-72-01203
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3892 Old Church Trl
Owner: Taylor Vance
Parcel 027-72-01203