Approved

Filed May 16, 2025 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 16, 2025
Assembly type
RP
Serial number
W191830
Size
4
Test gauge serial
G-8184
Gauge calibration date
Jan 7, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-79-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.