Back to the backflow review queue

Backflow assembly test: 4777 Laurel Trl

Approved

Filed May 6, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 6, 2026
Assembly type
PVB
Serial number
K233642
Size
1
Test gauge serial
G-3739
Gauge calibration date
Jan 17, 2026
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-77-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4777 Laurel Trl
Owner: Jamie Vance
Parcel 027-77-01256