Backflow assembly test: 1986 Cedar Hollow Ct
ApprovedFiled Jan 1, 2026 by Cameron Danner, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 1, 2026
- Assembly type
- RP
- Serial number
- W174547
- Size
- 1
- Test gauge serial
- G-3214
- Gauge calibration date
- Nov 4, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Danner, current on the service date
- All required fields present
- Address matches parcel 027-40-01033
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1986 Cedar Hollow Ct
Owner: Jordan Brandt
Parcel 027-40-01033