Backflow assembly test: Riverside Medical Offices
ApprovedFiled Aug 1, 2026 by Jordan Pruitt, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 1, 2026
- Assembly type
- RP
- Serial number
- A685797
- Size
- 4
- Test gauge serial
- G-7774
- Gauge calibration date
- Jun 24, 2026
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Pruitt, current on the service date
- All required fields present
- Address matches parcel 027-26-01176
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.