Back to the backflow review queue
Backflow assembly test: 603 Fox Run Way
ApprovedFiled Oct 22, 2025 by Avery Okafor, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 22, 2025
- Assembly type
- RP
- Serial number
- K126973
- Size
- 3/4
- Test gauge serial
- G-8194
- Gauge calibration date
- Jun 20, 2025
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Okafor, current on the service date
- All required fields present
- Address matches parcel 027-44-01354
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
603 Fox Run Way
Owner: Riley Hollins
Parcel 027-44-01354