Back to the backflow review queue

Backflow assembly test: 3877 Turkey Hill Dr

Sent back

Filed Nov 21, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 21, 2026
Assembly type
DC
Serial number
Z556147
Size
3/4
Test gauge serial
G-1676
Gauge calibration date
Sep 17, 2026
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-93-01310
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Sent back Please add the test gauge calibration certificate.

Property

3877 Turkey Hill Dr
Owner: Drew Fairley
Parcel 027-93-01310