Backflow assembly test: 5140 Meadow Lark Ln
ApprovedFiled Nov 20, 2024 by Avery Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 20, 2024
- Assembly type
- RP
- Serial number
- W965277
- Size
- 1
- Test gauge serial
- G-4831
- Gauge calibration date
- Apr 30, 2024
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Lindqvist, current on the service date
- All required fields present
- Address matches parcel 027-13-01239
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.