Back to the backflow review queue

Backflow assembly test: 292 Meadow Lark Ln

Approved

Filed Jul 19, 2024 by Avery Okafor, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 19, 2024
Assembly type
RP
Serial number
B852067
Size
1
Test gauge serial
G-1382
Gauge calibration date
Oct 30, 2023
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Okafor, current on the service date
  • All required fields present
  • Address matches parcel 027-82-01005
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

292 Meadow Lark Ln
Owner: Avery Nguyen
Parcel 027-82-01005