Back to the backflow review queue

Backflow assembly test: 8542 Orchard Ct

Approved

Filed Nov 29, 2024 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 29, 2024
Assembly type
DC
Serial number
W217797
Size
3/4
Test gauge serial
G-9022
Gauge calibration date
Oct 10, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-79-01050
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8542 Orchard Ct
Owner: Rowan Hollins
Parcel 027-79-01050