Backflow assembly test: 9020 Mill Creek Way

Approved

Filed Oct 2, 2025 by Quinn Wexler, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 2, 2025
Assembly type
PVB
Serial number
A397877
Size
3/4
Test gauge serial
G-8657
Gauge calibration date
Jun 30, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 027-96-01097
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.