Backflow assembly test: 9568 Turkey Hill Rd
ApprovedFiled Feb 23, 2025 by Quinn Wexler, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Feb 23, 2025
- Assembly type
- RP
- Serial number
- Z538303
- Size
- 1
- Test gauge serial
- G-8151
- Gauge calibration date
- Nov 6, 2024
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 027-93-01021
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9568 Turkey Hill Rd
Owner: Blake Danner
Parcel 027-93-01021