Back to the backflow review queue

Backflow assembly test: Station Brewing Co

Approved

Filed Jan 15, 2025 by Sam Fairley, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 15, 2025
Assembly type
RP
Serial number
K297963
Size
1 1/2
Test gauge serial
G-6480
Gauge calibration date
Sep 5, 2024
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Fairley, current on the service date
  • All required fields present
  • Address matches parcel 007-20-01126
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2603 Ridgeview Ln
Owner: Stroud Holdings LLC
Parcel 007-20-01126