Backflow assembly test: Station Brewing Co
ApprovedFiled Jan 4, 2026 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Jan 4, 2026
- Assembly type
- RP
- Serial number
- K297963
- Size
- 1 1/2
- Test gauge serial
- G-9581
- Gauge calibration date
- Feb 5, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Brandt, current on the service date
- All required fields present
- Address matches parcel 007-20-01126
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
2603 Ridgeview Ln
Owner: Stroud Holdings LLC
Parcel 007-20-01126