Back to the backflow review queue

Backflow assembly test: Station Brewing Co

Approved

Filed Jan 4, 2026 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jan 4, 2026
Assembly type
RP
Serial number
K297963
Size
1 1/2
Test gauge serial
G-9581
Gauge calibration date
Feb 5, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
3.2 psid
Relief valve opened at
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-20-01126
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2603 Ridgeview Ln
Owner: Stroud Holdings LLC
Parcel 007-20-01126