Backflow assembly test: 375 Meadow Lark Rd

Approved

Filed May 24, 2026 by Parker Danner, Valley Backflow Testing. Filed from a phone.

Report

Date of service
May 24, 2026
Assembly type
PVB
Serial number
W572583
Size
1
Test gauge serial
G-6197
Gauge calibration date
Jan 20, 2026
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-87-01031
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

375 Meadow Lark Rd
Owner: Riley Nguyen
Parcel 007-87-01031