Back to the backflow review queue

Backflow assembly test: 4366 Ridgeview Ln

Approved

Filed Oct 7, 2024 by Emerson Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 7, 2024
Assembly type
DC
Serial number
W523073
Size
1
Test gauge serial
G-5608
Gauge calibration date
Feb 21, 2024
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-71-01079
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4366 Ridgeview Ln
Owner: Shawn Fairley
Parcel 007-71-01079