Backflow assembly test: 4366 Ridgeview Ln
ApprovedFiled Nov 7, 2026 by Emerson Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 7, 2026
- Assembly type
- DC
- Serial number
- W523073
- Size
- 1
- Test gauge serial
- G-8922
- Gauge calibration date
- May 23, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Brandt, current on the service date
- All required fields present
- Address matches parcel 007-71-01079
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.