Backflow assembly test: Golden Diner

Approved

Filed May 5, 2025 by Emerson Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 5, 2025
Assembly type
RP
Serial number
B837086
Size
1 1/2
Test gauge serial
G-8324
Gauge calibration date
Jan 19, 2024
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2 psid
Relief valve opened at
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-30-01234
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4954 Orchard Dr
Owner: Harlow Holdings LLC
Parcel 007-30-01234