Back to the backflow review queue

Backflow assembly test: 6459 Turkey Hill Trl

Approved

Filed Dec 1, 2024 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Dec 1, 2024
Assembly type
RP
Serial number
A246838
Size
1
Test gauge serial
G-8145
Gauge calibration date
Feb 21, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-17-01271
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6459 Turkey Hill Trl
Owner: Avery Ellery
Parcel 007-17-01271