Backflow assembly test: Blue Heron Grill

Approved

Filed Nov 26, 2024 by Parker Danner, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 26, 2024
Assembly type
RP
Serial number
W754061
Size
1 1/2
Test gauge serial
G-3136
Gauge calibration date
Mar 26, 2024
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-88-01160
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6179 Quarry Way
Owner: Calloway Holdings LLC
Parcel 007-88-01160