Back to the backflow review queue
Backflow assembly test: 3625 Ridgeview Ct
ApprovedFiled Mar 15, 2025 by Parker Danner, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 15, 2025
- Assembly type
- DC
- Serial number
- A906639
- Size
- 1
- Test gauge serial
- G-5768
- Gauge calibration date
- Dec 12, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Danner, current on the service date
- All required fields present
- Address matches parcel 007-98-01248
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3625 Ridgeview Ct
Owner: Riley Wexler
Parcel 007-98-01248