Back to the backflow review queue

Backflow assembly test: 7898 Orchard Rd

Approved

Filed Aug 12, 2024 by Parker Danner, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 12, 2024
Assembly type
RP
Serial number
A207995
Size
3/4
Test gauge serial
G-4049
Gauge calibration date
Dec 7, 2023
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-61-01040
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7898 Orchard Rd
Owner: Logan Wexler
Parcel 007-61-01040