Backflow assembly test: Maple Leaf Grill

Approved

Filed Nov 19, 2025 by Parker Danner, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 19, 2025
Assembly type
RP
Serial number
W347786
Size
1 1/2
Test gauge serial
G-8519
Gauge calibration date
Jul 13, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-14-01328
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.