Backflow assembly test: Maple Leaf Grill
Needs reviewFiled Nov 25, 2026 by Jamie Wexler, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 25, 2026
- Assembly type
- RP
- Serial number
- W347786
- Size
- 1 1/2
- Test gauge serial
- G-3533
- Gauge calibration date
- Jun 30, 2026
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Wexler, current on the service date
- All required fields present
- Address matches parcel 007-14-01328
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
7687 Orchard Trl
Owner: Harlow Holdings LLC
Parcel 007-14-01328