Backflow assembly test: 4715 Quarry Dr

Approved

Filed Sep 19, 2024 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Sep 19, 2024
Assembly type
RP
Serial number
K948015
Size
1
Test gauge serial
G-2192
Gauge calibration date
Jun 25, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-71-01033
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4715 Quarry Dr
Owner: Morgan Benton
Parcel 007-71-01033