Back to the backflow review queue

Backflow assembly test: 8864 Stone Gate Trl

Approved

Filed Nov 4, 2025 by Cameron Whitcomb, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 4, 2025
Assembly type
RP
Serial number
W572117
Size
3/4
Test gauge serial
G-9241
Gauge calibration date
Sep 10, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-75-01049
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8864 Stone Gate Trl
Owner: Parker Brandt
Parcel 045-75-01049