Back to the backflow review queue
Backflow assembly test: Main Street Market
ApprovedFiled Dec 31, 2023 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 31, 2023
- Assembly type
- RP
- Serial number
- W656187
- Size
- 4
- Test gauge serial
- G-9625
- Gauge calibration date
- Sep 23, 2023
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Whitcomb, current on the service date
- All required fields present
- Address matches parcel 045-42-01322
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3280 Pine Knoll Rd
Owner: Calloway Holdings LLC
Parcel 045-42-01322