Back to the backflow review queue

Backflow assembly test: Main Street Market

Approved

Filed Dec 31, 2023 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 31, 2023
Assembly type
RP
Serial number
W656187
Size
4
Test gauge serial
G-9625
Gauge calibration date
Sep 23, 2023
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-42-01322
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3280 Pine Knoll Rd
Owner: Calloway Holdings LLC
Parcel 045-42-01322