Back to the backflow review queue

Backflow assembly test: Main Street Market

Approved

Filed Jan 18, 2025 by Drew Vance, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 18, 2025
Assembly type
RP
Serial number
W656187
Size
4
Test gauge serial
G-5172
Gauge calibration date
Jul 2, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 045-42-01322
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3280 Pine Knoll Rd
Owner: Calloway Holdings LLC
Parcel 045-42-01322