Backflow assembly test: 4090 Fox Run Trl

Approved

Filed Oct 18, 2026 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 18, 2026
Assembly type
RP
Serial number
Z153466
Size
3/4
Test gauge serial
G-5341
Gauge calibration date
Feb 2, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-83-01114
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.