Backflow assembly test: 8863 Fox Run Rd

Approved

Filed Sep 19, 2026 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 19, 2026
Assembly type
PVB
Serial number
W462198
Size
3/4
Test gauge serial
G-7434
Gauge calibration date
Apr 12, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ellery, current on the service date
  • All required fields present
  • Address matches parcel 045-36-01354
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8863 Fox Run Rd
Owner: Morgan Kessler
Parcel 045-36-01354